Medium Voltage Switchgear Room Design Guide (2024)

By Steven McFadyen on


Many medium voltage (MV) indoor switchgear rooms exist worldwide. The complexity of these rooms varies considerably depending on location, function and technology adopted by the owner. This article provides general guidance on the factors to be considered in the design of a typical room.

Typical Switchroom Equipment

Switchboards

The positioning of indoor MV switchboards requires careful consideration. Suitable access around the switchboard for maintenance, withdrawing of circuit breakers, safety and regulatory compliance needs to be allowed. Under fault conditions many switchgear require a minimum clear space above for the venting of gases. Attention needs to be given to the fixing down of switchboards and cable entry into and out of the switchboards.

Protection Panels

While relays can be incorporated within the switchboards, often they are installed in separate panels/racks. Provision needs to be made for the installation of any protection panels and control cabling to the associated switchboards.

Auxiliary Systems & Other Considerations

In addition to major equipment, there is whole host of other systems and issues which need to be considered in the design of any given installation:

Earthing & Lightning Protection - given the high levels of fault current associated with MV switchrooms, consideration of the earthing (grounding) is an important aspect of the design. Earthing systems need to provide adequate paths for fault current, ensure sufficient current for relay operation and limit step and touch potentials to safe values. Lightning protection if necessary needs to be installed and coordinated with the earthing system to provide a safe means to discharge any strike to ground.

SCADA - modern relays, switchgear and automation rely heavily on SCADA systems for operation and engineering access. These can become quite significant requiring equipment racks and associated cable distribution.

DC Systems – protection relays often work with dc supplies. Space provision for suitable dc supplies (rectifier, controls, batteries, etc.) needs to be considered in developing the switchroom layout.

Cable Containment – power MV cabling, low voltage cabling, control and SCADA cabling and optical fibres all require to be routed between equipment as well as into and out of the building. This can require significant space in terms of cable ladders and trenching. In many installation basem*nt or below floor space is utilised for cable containment.

Building Services - whilst the purpose of the switchroom is to hold the MV equipment, building services (lighting, small power, fire detection and protection, ventilation and air-conditioning, security and access control all need to be considered and provided where appropriate. To provide the building services an external low voltage supply will be required.

EMF - there is a growing concern over the effect of EMF on the human body. Where people have access to areas surrounding switchrooms cable distribution paths it is necessary to establish that the associated EMF levels are below recommended limits.

Switchroom Layout

Switchrooms are built to house switchgear and associated systems (cables, dc systems, SCADA and cable containment). Suitable provision should be made within the room for all these systems. In addition requirements such as toilets, desks, telephones, security systems, etc. may need to be considered.

Much of the equipment located within the switchroom is large and heavy. Suitable provision should be made for access to the switchroom, entrance into the room and moving the equipment around. Installation and removal of individual items of equipment should be possible with the switchroom live. Care needs to be taken around columns and other obstructions to ensure that clearance distances are maintained.

It is good practice (and a regulatory requirement in many countries) to provide at least two means of emergency egress. Doors providing emergency egress should open outwards.

Entry/exit to the building needs to be considered carefully to ensure suitable access and that water does not leak/enter the room.

Switchgear Room Dimensioning

Each switchroom is unique and needs to be considered in relation to the specific equipment which will be installed. As an illustration, the diagram below shows simple room layout consisting of a 22 kV switchboard, some DC and SCADA panels (click for a larger image).

The layout illustrates some of the key dimensions and issues to be considered:

Circuits – the room has been designed for a 22 kV system of five circuits and a bus-coupler, give a total of seven panels (two for the bus-coupler). Depending on actual number of circuits the room width can be easily expanded or reduced. Provision has also been made for the installation of future panels.

Switchboard Size – the arrangement is based on 600x1000mm panels. Should the actual panels be larger the necessary adjustments would have to be made.

Clearances – minimum statutory clearances always need to be observed. In addition to statutory limits, the designer needs to ensure there is adequate clearance for operational and maintenance requirements – often these would be larger than statuary minimums.

Front Entry – the scheme shown allows for access to the rear of the switchboard. Should the switchboard require only front access, the rear space could be reduced (to say 100 mm, just keeping the switchboard from the wall).

Height – sufficient height needs to be allowed to ensure adequate movement and operation of the switchboards. In practice, a height of 3700 mm is typical. Depending on type of switchboard this may need to be increased to allow for the exhaust of arc gasses during fault conditions.

Not shown on the example is lighting and air-conditioning systems. Given a room height of 3700 mm and space shown as the front of the layout, there is sufficient space to easily accommodate these.

See Also

  • Low Voltage Switchroom Design Guide
Medium Voltage Switchgear Room Design Guide (2024)

FAQs

What is the standard for switchgear design? ›

IEC 61439 is an international standard for the design and construction of low-voltage switchboards used in electrical power systems. It provides guidelines for the selection and installation of electrical components, such as circuit breakers, fuses, and busbars, to ensure safe and reliable operation of the switchboard.

What are the standards for medium voltage switchgear? ›

ANSI and IEEE standards define voltage classifications as follows: Low-voltage: up to 600V. Medium-voltage: between 600V and 69 kV. High-voltage: between 69 kV and 230 kV.

What is the height of a switchgear room? ›

The minimum room height for MCset switchgear is 4m from floor to ceiling.

What is the code for switchgear? ›

NAICS Code 335313 Switchgear and Switchboard Apparatus Manufacturing | IBISWorld.

How do I choose a switchgear? ›

In this article, we will provide a comprehensive guide on how to choose switchgear, covering essential factors to consider during the selection process.
  1. Identify the Load Type. ...
  2. Determine the Voltage Level. ...
  3. Assess Power Density. ...
  4. Consider Safety Requirements. ...
  5. Evaluate Brand and Quality. ...
  6. Evaluate Cost-Benefit Analysis.
Sep 20, 2023

What is medium voltage per NEC code? ›

Medium Voltage Systems (MV): 2,400 to 69,000 VAC (ANSI), Greater than 600 nominal V(NEC), Greater than 1000 Volts, up to 35000 Volts (IEEE 1547-2018).

What is the basic of medium voltage switchgear? ›

Medium voltage switchgear is a critical component of electrical power systems, used to control and protect electrical equipment and circuits in the voltage range of 1kV to 36kV. It typically consists of circuit breakers, disconnectors, fuses, relays, and other accessories, all housed within a metal enclosure.

What is the IEC standard for MV switchgear? ›

This part of IEC 62271 specifies requirements for prefabricated metal-enclosed switchgear and controlgear for alternating current of rated voltages above 1 kV and up to and including 52 kV for indoor and outdoor installation, and for service frequencies up to and including 60 Hz.

What are the requirements for a switchgear room door? ›

For equipment rated 1200 amperes or more and over 1.8 m (6 ft) wide that contains overcurrent devices, switching devices, or control devices, there shall be one entrance to and egress from the required working space not less than 610 mm (24 in.) wide and 2.0 m (61∕2 ft) high at each end of the working space.

What is the NEC code for electrical rooms? ›

NEC Table 110.26(A)(1) provides the minimum clearances required for working space in an electrical room, and the following apply in the case of 0-600V installations: 3 feet between insulated materials. 3-½ feet between grounded equipment. 4 feet between exposed live parts.

What is typical switchgear height? ›

Switchgear is 96-inches tall, minimum depth is 54 inches, standard depth is 72 inches. Rear-access design is standard, with options for front-access and arc-resistant constructions. All breakers are drawn-out and require breaker lifting device. Switchboards are 90-inches tall with a minimum depth of 18 inches.

What is a switchgear room? ›

In an electric power system, switchgear/switchboards and motor control rooms are the combination of electrical disconnect switches, fuses, or circuit breakers used to control, protect, and isolate electrical equipment.

What is the standard for switchgear? ›

Low-voltage switchgear carries the following ratings:

Power frequency (Typically 50Hz and 60Hz) Insulation level (Typically 2.2kV) Continuous current (Typically up to 10,000A) Short-circuit withstand current (Typically up to 200kA)

What size is a medium voltage switchgear? ›

The switchgear will be One/Two high construction with indoor frame size of 36” wide x 95” high x (standard – 85”, optional – 92”) deep.

What is the UL standard for switchgear? ›

Additionally, many building codes and electrical codes also require switchgear assemblies to be certified to the UL 891 standard. UL 891 Switchgear is a critical standard to protect the safety of operators, maintenance personnel, and the public from hazards arising from electrical distribution systems.

What is the IEC standard for LV switchgear? ›

The IEC 61439 standard. All low-voltage switchgear and controlgear assemblies in the European Economic Area are required to comply with the IEC 61439 standard. The standard describes the design verification for controlgear assemblies and the responsibilities of the manufacturer and switchboard manufacturer.

Is 8623 vs IEC 61439? ›

Indian Standard IS-8623 & IEC-60439 was exactly similar in all respect but a new IEC-61439 was first published in 2009 & re-launched in 2011. After 5 years of transition period International Electrotechnical Commission has made the IEC-60439 obsolete but IS-8623 is still in use.

What is switchgear design? ›

Switchgear is a broad term that describes a wide variety of switching devices that all fulfill a common need: controlling, protecting, and isolating power systems. This definition can be extended to include devices to regulate and meter a power system, circuit breakers, and similar technology.

Top Articles
Latest Posts
Article information

Author: Aracelis Kilback

Last Updated:

Views: 5532

Rating: 4.3 / 5 (64 voted)

Reviews: 95% of readers found this page helpful

Author information

Name: Aracelis Kilback

Birthday: 1994-11-22

Address: Apt. 895 30151 Green Plain, Lake Mariela, RI 98141

Phone: +5992291857476

Job: Legal Officer

Hobby: LARPing, role-playing games, Slacklining, Reading, Inline skating, Brazilian jiu-jitsu, Dance

Introduction: My name is Aracelis Kilback, I am a nice, gentle, agreeable, joyous, attractive, combative, gifted person who loves writing and wants to share my knowledge and understanding with you.